Smoke Management.

Stairwell pressurisation, smoke extraction, atrium smoke control and the dampers that compartmentalise fire spread.

Systems & scope

What this covers.

Stairwell pressurisation

Fan-and-damper systems maintaining 50 Pa positive pressure in escape stairs. Variable-speed fans with relief dampers to prevent over-pressurisation.

Smoke extraction

Mechanical smoke extract fans on affected zones, with motorised dampers releasing on alarm. Sized to clear smoke layer above the egress plane.

Fire & smoke dampers

UL-listed fire dampers and smoke dampers in HVAC ductwork at fire-compartment boundaries. Motorised closure on alarm; fail-safe spring-return.

Engineering approach

Stairwell pressurisation is designed against the door-opening scenario most adverse — typically all doors closed (max pressure) and one door open (min pressure). Per NFPA 92.

Atrium smoke control uses CFD modelling (Ansys Fluent) where the volume, geometry and stratification matter. Make-up air sources are interlocked to prevent smoke being pushed back into the protected zone.